Select language: zh-CNesdefrja

Water Reclamation - Local Limits

For more information about these industrial limits, contact the WRF via telephone at the information listed to the right.

Metals:
Cadmium 0.136 mg/L Lead 0.581 mg/L
Chromium 3.362 mg/L Nickel 2.880 mg/L
Copper 1.508 mg/L Zinc 8.303 mg/L
Iron 50.0 mg/L Mercury 0.0 ug/L *

* 0.0 ug/L is the actual limit for mercury. However, an industry discharging wastewater containing a concentration of 0.5 ug/L or less will be considered in compliance.

Sewer Use Code:
Oil & Grease (Total) 200 mg/L pH 5 to 10 SUs
Oil & Grease (TPH)  100 mg/L Temperature 104 °F

Surcharge:
Chemical Oxygen Demand (COD) 400 mg/L Ammonia (NH3) 25 mg/L
Biochemical Oxygen Demand (BOD) 300 mg/L Phosphorus (P) 20 mg/L
Total Suspended Solids (TSS) 250mg/L    

Revision Effective 09/20/07

Home > City Services > Water Reclamation > Industrial Limits